Eltek WebPower
The Eltek WebPower is an adapter that makes it possible to monitor and control DC power systems.
About
The connector consists of different pages representing the different aspects of this device that can be monitored and controlled, for example Inputs, Outputs, Voltage, etc.
Information is polled from the device using SNMP calls. In addition, the original web interface of the device is available through the connector.
Version Info
| Range | Description | DCF Integration | Cassandra Compliant |
|---|---|---|---|
| 1.0.0.x | Initial version | Yes | Yes |
Product Info
| Range | Supported Firmware Version |
|---|---|
| 1.0.0.x | Unknown |
Installation and configuration
Creation
SNMP Main Connection
This connector uses a Simple Network Management Protocol (SNMP) connection and requires the following input during element creation:
SNMP CONNECTION:
- IP address/host: The polling IP of the device.
SNMP Settings:
- IP port: The IP port of the device.
- Get community string: The community string used when reading values from the device, by default public.
- Set community string: The community string used when setting values on the device, by default private.
Usage
General
This page displays general information about the device, such as DC Plant Information, the System Date and Time, and some monitored values related to the Battery and Voltage.
Control Units
This page displays information related to the Control Unit Temperature and Fan Speed alarm states.
Rectifiers
This page displays information about the rectifiers. This includes the Rectifier Status Table, which displays information such as the Rectifier Status, Output Current, Output Voltage and Rectifier Temperature.
Solar Chargers
This page displays information about the rectifiers. This includes the Solar Charger Status Table, which displays information such as the Solar Charger Status, Output Current, Output Voltage and Solar Charger Temperature.
Load
This page displays information about the load, such as the Load Distribution Current and the Load Distribution Breaker Status. The page also contains two tables: the LVLD Table and the Load Monitor Units Table.
Battery
This page displays information about the battery, such as the Battery Status, the Energy Log and the Cycle Log. It also allows you to configure the Alarm Limits.
The page contains a number of page buttons. The page buttons Monitor Units, Battery Banks and LVBD provide access to a number of tables.
Network Settings
On this page, you can enable or disable the LITE mode.