Gamatronic UPS GMaCi
The UPS GMaCi is a UPS monitoring card from Gamatronic. This connector provides an interface for the card in DataMiner.
About
The GMaCi card for UPS systems allows continuous monitoring and control of these systems, with real-time detection of UPS faults and immediate notification through SNMP Traps. By polling the card from DataMiner, it is possible to add alarming and trending on values, adjust operational settings, and integrate the device in the DataMiner System.
Installation and configuration
This connector primarily uses an SNMP connection and needs the following information:
SNMP CONNECTION:
- IP address/host: The polling IP of the device, e.g., 10.11.12.13.
SNMP Settings:
- Port number: The port of the connected device, by default 161.
- Get community string: The community string in order to read from the device. The default value is public.
- Set community string: The community string in order to set to the device. The default value is private.
Usage
The layout of the connector is similar to that the web interface, but there is an additional page named General, which contains the Identification parameters from the UPS page, in order to reduce the number of parameters on the latter.
Since the SNMP interface does not allow for reading or editing of values found on the Configuration page and subpages from the web interface, these values are not included in the connector.
UPS
This page contains the following parameter groups:
- Nominal values: Nominals
- Battery Status: Battery
- Input readings: UPS Input Table
- Output readings: Output Source, Output Frequency and UPS Output Table
- Bypass readings: Bypass Frequency and UPS Bypass Table
Control
With the UPS Control group, the device can be configured to reboot after it was shut down on request or after a power failure. This is done by changing the parameter Auto Restart. Furthermore, the device can be forced to stop or restart with different types of delays.
The UPS Test group shows the latest test results and indicates whether a test is currently running.
To run a test, select the type in Selected Test Id and then click Start Selected Test.
Alarms
This page will show any active alarm on the device. With the Alarms Present counter you can monitor whether an alarm is present.
Webpage