Configuring hysteresis in an alarm template
Two types of hysteresis are available, clear hysteresis and alarm hysteresis, respectively having an effect on the clearing and on the triggering of alarms:
Enter a value in the Hyst off column to determine the number of seconds before the severity level of an alarm decreases.
Enter a value in the Hyst on column to determine the number of seconds before the severity level of an alarm increases.
If you want to apply hysteresis to specific severity levels only, when you enter a value in the Hyst off or Hyst on box, select the severity levels in the drop-down list below the box.
Note
- For most parameters, the hysteresis interval has to be higher than the polling interval. For example, if a parameter is only polled every 10 seconds, you should not configure a hysteresis interval of 5 seconds. However, an exception to this are parameters updated via traps or via a smart-serial connection.
- For parameters of type string, hysteresis should only be applied to "high" severity levels (e.g. Warning High, Major High), not to "low" severity levels. From DataMiner 10.1.9/10.2.0 onwards, applying hysteresis to "low" severity levels is no longer possible for string parameters.
Tip
See also: Alarm templates – Hysteresis on DataMiner Dojo